Hardware Verification

Which device behaviours are confirmed on real hardware, which are assumed, and what that means for the service. This page is the single place for verification status; other pages link here instead of repeating it.

Status Meaning
Verified Confirmed by a measurement on a real inverter. The service relies on it.
Per-device Verified for one inverter by the background service or a measured Expert override.
Observed Seen on hardware and handled defensively, but not a guaranteed contract.
Assumed A documented working assumption; the service behaves conservatively.
Unverified No hardware evidence. The dependent feature is off, blocked or marked as unverified.
Unsupported Not decoded or not used.

Verification matrix

Consumption history

Feature or assumption Status Evidence and consequence
logger_day_eload_log_ts unit and day mapping Verified Wh per local calendar day (A/B measurement below). The daily backfill is always on.
Day-point timestamps Verified Local wall-clock fields, labelled UTC.
before= query boundary Observed A/B on the tested inverter (2026-10-18) returned the boundary point only for local wall-clock fields encoded as UTC; do not generalize to other devices without checking.
Repeated 23:59:59 logger points Observed The logger may repeat one day's last point 8 to 16 times with values differing by under 1 Wh; the largest value wins.
Other logger registers (for example logger_minutes_eload_log_ts) Unverified Grid and unit not clarified; not used anywhere.
Year and month history (logger_year_eac_log_ts, logger_month_eac_log_ts) for the battery commissioning date Unverified Query contract not confirmed on hardware. Automatic derivation stays disabled; an operator-entered date always works.
Event tables (logger_error_log_time_stamp) Unsupported Classified read-only; the wire format is not decoded and neither unit nor timestamp semantics are verified.
Day counter reset instant and time zone Unverified Only "non-decreasing between resets" is assumed.
Total counter reset or overflow behaviour (energy_e_load_total) Unverified Resets, deltas above 50 kW, stalled counters and gaps over 24 h are rejected and counted.
Whether the load counter includes external power Unverified Not assumed either way.

Battery dispatch

Feature or assumption Status Evidence and consequence
Battery dispatch write path (write_path_convention) Per-device Needs the SoC strategy code, enum and bool byte widths, frame layout and apply sequence. Dispatch stays blocked until verified, except in engineering mode.
Battery and grid power sign conventions Per-device Verified together with the write path; defaults are assumptions.
Hold behaviour (hold) Unverified Not demonstrated on the unit. The same capability gate applies. See Battery Control.
Export limit convention Per-device Not part of the verification form; matters only with limit_export_during_discharge (off by default).
Live charge limit register Unsupported The producer always reports no live limit; the static device limit governs.
Reference of power_mng_battery_power_extern (battery side or AC side) Assumed Plan assumes battery-side, power_reference_verified: false.
Charge efficiency (90 %) and preferred power range Assumed Planning assumptions, not device properties.

Battery capacity

Feature or assumption Status Evidence and consequence
Capacity ratio power_mng_amp_hours_measured / battery_ah_capacity Unsupported Hardware reads varied from 25.0/23.8531 Ah at 79–87 % SoC to 16.9251/8.65005 Ah near 2.5 % SoC. No automatic current capacity or calibration point is released.
Ah register readability on RCT DC 10.0, firmware 2.3.5689 Observed Both registers returned values during the 2026-10-17 characterization run. This does not validate their usable-Wh semantics.
Per-tower versus device-wide meaning of battery_placeholder_0_ah_capacity and other battery registers Unverified Unsupported tower combinations stay unavailable.
Lifetime Wh counters battery_stored_energy / battery_used_energy and battery_efficiency Observed Their ratio matches the efficiency of the official RCT installer app on the tested inverter (see Installer-app counter comparison). Throughput, not capacity.
Lifetime throughput as current usable capacity (Wh per cycle, stored minus used energy) Unsupported Lifetime throughput is not present usable capacity. No capacity is derived from it.
battery_soh scale and conversion Unverified The protocol names it State of Health (battery.soh); scale and conversion to usable Wh are not verified. Recorded, not used.
battery_status and battery_bat_status as calibration indicators Unverified Both are recorded as additional BMS-state evidence, but no calibration meaning has been established.
Calibration registers (power_mng_calib_charge_power, power_mng_bat_calib_*, bat_mng_struct_bat_calib_soc_thresh*) Unverified Named in the protocol; none is verified as "last calibrated usable capacity". Recorded read-only, not used.
power_mng_battery_type codes Unsupported Not used.

Protocol

Feature or assumption Status Evidence and consequence
net.slave_data decoding Verified One device, firmware 2.3.5687: 108 bytes, all numeric fields little-endian.
CRC escaping, frame layout of commands 0x08/0x48, byte width of t_enum/t_bool, string encoding Unverified Documented as not yet verified against a real inverter; verify before production use.
Origin of unsolicited response frames Unverified Working hypothesis only; see Transport Diagnostics.

Device-specific characterization: 2026-10-17

Device: RCT DC 10.0 Steiner, firmware 2.3.5689. These observations apply to this device and run.

Observation Status Evidence and limit
Primary tower topology Observed Three inventory passes found six populated module serial slots (0–5); slot 6 was empty.
Second tower Observed Classified absent during this run.
power_mng_n_batteries Observed Read as 1, consistent with the observed single tower.
Ah registers Observed power_mng_amp_hours_measured read as 23.8530769348 Ah and battery_ah_capacity as 25.0 Ah. Both reads succeeded; later readings at low SoC differed, so their ratio is not an established usable-capacity health factor.
Normal reads Observed battery_soc_target and household_load_power succeeded at approximately T+5, T+30, T+60 and T+300 seconds: eight successful reads without a reconnect. No instability was reproduced in this five-minute run.
READ_PERIODICALLY registration Not exercised in these runs The probe ran read-only (invasive = false, registration_probes empty, "No periodic registration was made"), so no registration was attempted; this run neither confirms nor denies a registration failure.
Periodic push delivery and subscription persistence Unverified The probe did not write pas.period, observe subsequent push cycles or test a reconnect.

The 23.8530769348/25.0 Ah ratio would make the six-module rated baseline approximately 9.89 kWh if used as a health factor. That calculation alone is not an independent charge/discharge capacity measurement or proof of the registers' physical meaning; the service does not release that ratio as automatic current capacity.

Day-history query-boundary A/B measurement

Boundary 2026-10-16, Europe/Berlin, read-only (tools/probe_consumption_history.py):

Run before= value Meaning 2026-10-15 day point
A 1792101600 True UTC instant of local midnight missing
B 1792108800 Local wall-clock encoded as UTC present

The boundary point was absent in A and present in B on the repeat run of 2026-10-18; its value, 18018.6797 Wh, matches the operator's export. This confirms the local-wall-clock query encoding on the tested inverter only. The production history provider already encodes local clock fields as a UTC-labelled query instant. See Consumption for current usage.

Characterization run: 2026-10-17

Device-specific evidence from a single read-first run. It characterizes one unit and one firmware; it does not generalize to every RCT DC 10.0 or every firmware.

  • Device: RCT DC 10.0 Steiner
  • Firmware: 2.3.5689
  • Mode: read-only (tools/diagnostics/rct_battery_probe.py)

Battery topology (this device)

Observation Status
Primary tower present with six populated module serial slots (0–5) Observed on this device
Primary tower slot 6 empty; three inventory passes Observed on this device
Placeholder tower absent (no populated module serials) Observed on this device
power_mng_n_batteries = 1 Consistent with the observed topology

The placeholder tower reports present = false with module_count = null and module_count_status = pending; present is the authoritative signal here. pending on an absent tower means "no module serials seen", not "a scan is still running"; the regular dashboard filters absent towers out, so it never shows a scan state for one.

Capacity registers (this device)

power_mng_amp_hours_measured ≈ 23.853 Ah and battery_ah_capacity = 25.0 Ah were both read successfully. One read of power_mng_amp_hours_measured later in the same run timed out; the cache freshness and retry handling absorb such a single timeout. At the time of this run the service still scaled the rated capacity by the Ah ratio (6 × 1.92 kWh × 0.9 × 23.853 / 25 ≈ 9.89 kWh). That is historical: the ratio proved SoC-dependent (see above), so the service now uses the rated usable capacity of the module topology only, 6 × 1.92 kWh × 0.9 ≈ 10.37 kWh.

Calibration evidence recording

To find out which register proves a completed BMS calibration, the service records read-only evidence per inverter in daily files battery-diagnostics/battery-diagnostics-YYYY-MM-DD.jsonl next to the admin database (UTC days; finished days are gzip-compressed, files older than 60 days are deleted). Each line has a type, a UTC timestamp, a monotonic time, the device, inverter and BMS identity and the rated capacity of the settled module inventory:

type Content
periodic_fast Every 15 s from the cache, no extra device read: battery_soc, battery_power, battery_status2
periodic_counters Every minute, read fresh: the four cumulative Wh/Ah counters (battery_stored_energy, battery_used_energy, battery_charged_amp_hours, battery_discharged_amp_hours)
periodic_slow Every 5 minutes, read fresh: both Ah capacity candidates, power_mng_amp_hours, battery_soh, battery_cycles, battery_status2, battery_status, battery_bat_status, power_mng_bat_next_calib_date, power_mng_calib_charge_power, battery_efficiency, battery_bms_sn
periodic_config On the first recorder tick for each inverter and then every 24 hours, read fresh: power_mng_bat_calib_reqularity, power_mng_bat_calib_days_in_advance, bat_mng_struct_bat_calib_soc_thresh, bat_mng_struct_bat_calib_soc_threshold
status_transition When the cached battery_status2 changes: all counter, slow and calibration-configuration values, with the status before and after
candidate_change A fresh power_mng_bat_next_calib_date differs from its previous fresh value: register, before, after
calibration_window_hint A battery_status2 transition where either side has a community-observed "Calibrating" bit (0x008, 0x400)

Cached values carry status, age_seconds, sample_monotonic and sample_measured_at; fresh reads carry status and measured_at. Every value carries a status (fresh, stale, missing, error, skipped_busy while the device queue is busy, not_in_catalog); gaps are never filled in or interpolated. battery_status and battery_bat_status are additional BMS-state evidence; their calibration meaning is unverified. The SoC-dependent Ah values and battery_soh remain in the raw periodic_slow records without change events or a float threshold. candidate_change and calibration_window_hint are marked evidence_only: true and verified: false: they say where to look, not that a calibration finished or what it measured. When an inverter is re-addressed in the settings, its schedule and last-seen comparison state are reset, and reads still in flight for the old address are discarded, so records never mix two devices. The recording changes nothing the service plans or reports: neither the planner, Battery Health nor calibration_sample() reads it, and no register is written.

The open question for the next regular BMS calibration: which value changes reproducibly at the calibration event and then stays stable across different SoC? Only a value with that evidence can become a calibration sample, in a separate change.

Installer-app counter comparison (this device)

The official RCT installer app showed on the tested inverter:

Value Installer app
Stored (charged) energy 9,814,451 Wh
Used (discharged) energy 9,162,862 Wh
Battery efficiency 0.93
Cycles 1101
Preceding Ah counter (label cropped in the screenshot; likely charged Ah) ~19,016.32 Ah
From-battery Ah (labelled "Gesamtladefluss von der Batterie") 18,233.95 Ah

Topology: six modules, rated usable capacity 10.368 kWh.

9,162,862 / 9,814,451 = 0.9336

This strongly supports the current mapping of the cumulative Wh counters and battery efficiency on this tested inverter. It does not prove present usable battery capacity.

  • Lifetime energy throughput is not present usable capacity, and neither is Wh per cycle.
  • battery_stored_energy - battery_used_energy is not a capacity either.
  • The Ah ratio power_mng_amp_hours_measured / battery_ah_capacity stays Unsupported: it is SoC-dependent.
  • battery_soh is officially named State of Health, but its scale and conversion are unverified.
  • The calibration registers are officially named, but no register is verified yet as the last calibrated usable capacity.

Normal reads (this device)

Over a five-minute window, battery_soc_target and household_load_power were read at roughly T+5 s, T+30 s, T+60 s and T+300 s — eight reads, all successful, with no reconnect. This run reproduced no normal-read instability; it does not prove normal reads are universally stable. The probe classifies the run as "no problem reproduced in this run", and one run is not a decision.

READ_PERIODICALLY: registration versus push delivery

Registration and actual push delivery are distinct behaviours and must not be conflated.

The probe artifacts for this characterization run (rct_battery_probe.py) were taken in the default read-only mode: periodic_status.registration_probes is empty and the run records "No periodic registration was made (default mode)" with invasive = false. The configured default set it reports (soc_target, household_load_power) is the intended periodic object set, not an executed registration. These runs therefore establish only stable normal reads (above); they do not exercise READ_PERIODICALLY registration, and periodic behaviour is explicitly "not tested in this mode".

Behaviour Status
READ_PERIODICALLY registration for the two probed objects Not exercised in these runs
Actual periodic pushes after setting pas.period Unverified
Persistence of a subscription across reconnect or session Unverified

Actual periodic push delivery was never exercised: it needs a pas.period write, which the read-only tool does not send. The working hypothesis about persisting subscriptions stays open; see Transport Diagnostics.

Verifying a device

  • Dispatch capabilities: the service verifies each device in the background when evidence is sufficient. Expert mode permits a measured override with a note; see Battery Control. Verifying one device never releases another.
  • Logger history: run the read-only probe with the application stopped: python tools/probe_consumption_history.py --host <DEVICE_HOST> --port 8899 --pages 8. It sends only logger history queries (a write frame on the wire that stores nothing) and never writes the device address into its output.
  • Production use: the service is the only intended client of port 8899; see Operation.