Operation

Running the service in production: what must hold, what to watch, how to back up. Device-specific verification status is on Hardware Verification; battery control is in Battery Control.

Production limits

Constraint Detail
One instance per inverter endpoint Device access is serialized only inside one process with one HTTP worker. Several instances against the same endpoint produce mixed or stale answers and there is no cross-instance lock: run exactly one replica per device group.
Exclusive access to port 8899 See below.
Plain HTTP TLS terminates at a reverse proxy; see Network and TLS.
Protocol assumptions Some are not yet verified against a real inverter; check Hardware Verification before production use.
Writes Off by default; enabled and approved per parameter in the GUI.

Exclusive access to port 8899

This service must be the only client of the inverter's port 8899; the vendor app, home automation or any other RCT client counts as foreign access. Exclusivity is not enforced: a suspicion is flagged (foreign_access_suspected in the readiness response, Prometheus gauge rct_transport_foreign_access_suspected) and the service keeps serving.

Maintenance state

When the inverter signals its bootloader, sending stops and requests for its devices get 503 device_maintenance until a cool-down has passed and a single read succeeds.

Runtime and restart behaviour

  • Most settings autosave in the GUI and take effect without a restart. A changed listen address or port is switched in the background; the inverter list and the TSDB export fields need Apply changes, which rebuilds the connections without a restart.
  • Until the initial admin password is changed, the service is idle: periodic reads, heartbeat polling, metric collection and the push export stay stopped, and start without a restart after the change.
  • A service restart hands every running Energy Manager command back to the inverter.
  • Write access can be switched off live; it sets every device to mode Off and hands the inverters back.
  • After adding or removing battery modules, restart the service so the module count is re-read.
  • A removed or re-addressed device loses its dispatch state (capabilities unverified, engineering mode off, Energy Manager mode Off).
  • Compose gives the container a one-minute stop grace period; the server runs as PID 1 and receives SIGTERM directly. See Docker.

Logs and health

  • Logs are text on stdout; Compose rotates them (50 MB, 5 files).
  • Access log level: GUI pages, assets, session polls and successful /metrics requests are DEBUG; mutating admin actions (login, password, settings, tokens), /api/ and /health are INFO; any 4xx is WARNING, any 5xx ERROR. Exception: the Energy page's device poll, whose expected 503 while write support is off is DEBUG.
  • The generated admin password appears in clear text in a boxed block on first start only (see Authentication). Change it at first login.
  • GET /health is token-free and turns 503 once shutdown has begun; the container health check queries it on the container's own address. It is a process check and says nothing about the inverter; use GET /api/v1/readiness for that.

Backup and restore

State lives in data/rct.db (settings, credentials, tokens, consumption and price history) and, for battery dispatch, data/rct-dispatch.db. Settings and credentials are stored encrypted; changing HMAC_SECRET prevents decryption. Back up database and secret together and restore them together (see Environment Variables).

The admin database runs in SQLite WAL mode (synchronous=NORMAL, 5 s busy timeout), so concurrent autosaves, sessions and token bookkeeping do not block each other. While the service runs, rct.db-wal and rct.db-shm may exist next to rct.db; they get the same 0600 permissions and are folded back into rct.db on a clean shutdown.

  • Back up while the service is stopped (copy all existing rct.db* files together) or online with sqlite3 data/rct.db ".backup backup.db". Never copy only rct.db of a running service.
  • Battery calibration evidence is written next to the database in battery-diagnostics/ (daily JSONL files, 60 days retained); it is optional diagnostic data, see Hardware Verification.
  • Keep the directory on a local file system. WAL does not work on NFS or SMB shares.
  • The directory must be writable (in Docker the rct-data volume), because SQLite creates the -wal and -shm files there.
  • Keep volume and secret across upgrades.
  • An older build rejects a migrated dispatch database; restore a backup to go back (Battery Control).

Admin dashboard

  • Edit dashboard opens edit mode on the Overview page (move and resize widgets, Add widget, Reset layout, Done); changes autosave. On a phone widgets are stacked and the layout cannot be edited (the saved layout stays untouched).
  • Each inverter card shows the energy-flow graphic (from cached readings, also with write support off), a power card and one card per battery tower. A tower's module count comes from its populated module serial slots: "Detecting modules..." until all slots were read, "Module layout unclear" instead of a drawing for a pattern no documented tower has (for example seven slots, where a Power Battery 11.5 has six modules). A tower with N modules is drawn as top cap, N-1 middle parts and bottom part.
  • The Energy Manager page shows a compact grid, house and battery energy-flow view beside the controls when space allows, from measured, sign-normalized readings.
  • If the server is unreachable, the dashboard keeps the last data (up to one hour old, dimmed, with a banner); a button-less "Connection lost" dialog probes the server and reloads the page once it answers.
  • The layout is stored in data/rct.db, separate from device settings, via GET/PUT/DELETE /admin/api/dashboard-layout (admin API, not public contract). The server accepts only known widget ids, at most 32 widgets and a 12-column grid.
  • The About page checks GitHub for a newer release: results are cached for 1 h, errors for 60 s, and a forced refresh runs at most once per 30 s.
  • /admin/static/ answers 404 for any path with a dot-prefixed segment.

Writes

  • Write support is enabled on the GUI Inverters page; the read/write role and the write selection in data/rct.db still apply. A fresh database starts with an empty selection (the shipped catalog only lists what may be enabled): tick each metric to allow, including action objects such as com_service.
  • "Documented in the catalog" is not "writable out of the box". The destructive com_service codes 6 erase_parameters_flash and 11 erase_datalog are not shipped as writable; codes 0, 5, 9, 10, 12, 13, 14, 15, 16, 18 are. To allow an erase action, copy the shipped file, add the code to its allowed_values and use it as the write allowlist (write_allowlist_path is not an environment setting).
  • Numeric limits are wire type limits, not safe operating limits or a promise that the firmware accepts a write.
  • The Inverters page shows a short explanation under a writable parameter where the catalog entry has a help_text. Most entries document only their vendor object path and intentionally have none rather than a guessed one; an own registry file can add help_text to any entry (the field is optional).
  • wifi_password is deliberately excluded: secrets are neither readable nor writable, and a registry or allowlist that lists it aborts the start.
  • Writing pas_period can change periodic polling.
  • Repeating an action requires resetting it to 0 first.
  • Battery dispatch has its own gates: Battery Control.