Operation

One instance per inverter endpoint

The serialization of device access is guaranteed only inside one process with one HTTP worker. Several instances against the same inverter endpoint violate it and produce mixed or stale answers. Run exactly one replica per device group; the service has no cross-instance lock.

Exclusive access to port 8899

Make sure this service is the only client of the inverter's port 8899. The vendor app, a home automation integration or any other RCT client counts as foreign access. The service does not enforce exclusivity; it flags a suspicion (foreign_access_suspected in the readiness response and the Prometheus gauge rct_transport_foreign_access_suspected) and keeps serving.

Maintenance state

When the inverter signals its bootloader, sending stops and requests for its devices get 503 device_maintenance until a cool-down has passed and a single read succeeds.

Logs and health

  • Logs are text on stdout; Compose rotates them (50 MB, 5 files).
  • The access log level depends on the request: GUI pages, assets, session polls and successful /metrics requests are DEBUG; mutating admin actions (login, password, settings, tokens), /api/ and /health requests are INFO; any 4xx is WARNING and any 5xx is ERROR.
  • The generated admin password is never logged. The boxed block printed to stdout after the server has started shows it in clear text (a deliberate operator choice, so it can be copied straight from the console on first start), and it is also saved to initial-admin-password next to the admin database (data/initial-admin-password by default, mode 0600) as a fallback for runs without a visible console. Change the password at first login, then delete the file.
  • GET /health is token-free and turns 503 once the shutdown has begun. The container health check queries it on the container's own address.

Admin dashboard

  • Edit dashboard opens the edit mode of the Overview page (move and resize widgets, Add widget, Reset layout, Done). Changes autosave. On a phone the widgets are stacked and the layout cannot be edited; the saved layout stays untouched.
  • Each inverter card shows the energy-flow graphic (from the cached readings, also with write support off), a power card and one card per battery tower. The module count of a tower is derived from its populated module serial slots; until all slots were read the card shows "Detecting modules…", and a slot pattern that cannot describe a documented tower shows "Module layout unclear" instead of a drawing.
  • The Energy Manager page shows a compact grid, house and battery energy-flow view beside the controls when space allows. Both views use measured, sign-normalized readings.
  • If the server cannot be reached, the dashboard keeps showing the last data (up to one hour old, dimmed, with a banner) and a "Connection lost" dialog without buttons probes the server in the background and reloads the page automatically once it answers again.
  • The layout is stored in data/rct.db, separate from the device settings, through GET/PUT/DELETE /admin/api/dashboard-layout (admin API, not part of the public contract). The server accepts only known widget ids, at most 32 widgets and a 12-column grid.
  • The About page checks GitHub for a newer release: results are cached for 1 h, errors for 60 s, and a forced refresh runs at most once per 30 s.
  • /admin/static/ answers 404 for any path with a dot-prefixed segment.

Writes

  • Write support is enabled on the GUI Inverters page; the read/write role and the write selection stored in data/rct.db still apply. A fresh database starts with an empty selection: the shipped catalog only lists what may be enabled, so tick each metric you want to allow, including action objects such as com_service.
  • The shipped allowlist separates "documented in the catalog" from "writable out of the box": a labeled action is not automatically a safe default. The destructive com_service codes 6 erase_parameters_flash and 11 erase_datalog are therefore not shipped as writable; the codes 0, 5, 9, 10, 12, 13, 14, 15, 16, 18 are. To allow an erase action anyway, copy the shipped file, add the code to its allowed_values and use that file as the write allowlist (write_allowlist_path is not an environment setting).
  • Numeric limits are wire type limits, not safe operating limits or a promise that the firmware accepts a write.
  • The Inverters page shows a short explanation under a writable parameter where the catalog carries one in the entry's help_text. Most entries document only their vendor object path, so they intentionally stay without an explanation rather than getting a guessed one; an own registry file can add help_text to any entry. The field is optional, so a registry written without it keeps loading.
  • wifi_password is deliberately excluded: secrets are neither readable nor writable, and a registry or allowlist that lists it aborts the start.
  • Writing pas_period can change periodic polling.
  • Repeating an action requires resetting it to 0 first.

Measured values

  • Subnormal t_float readings preserve their IEEE 754 value and sign in the decoder.
  • Battery power, voltage and current are separate device variables; the power need not equal voltage times current.
  • Grid feed-in energies are passed through as the device sends them; the protocol defines no sign.

Verification status

Protocol assumptions (CRC escaping, frame layout of commands 0x08/0x48, byte width of t_enum/t_bool, string encoding) are not yet verified against a real inverter; do that before production use. net.slave_data is verified on one device with firmware 2.3.5687: 108 bytes, all numeric fields little-endian.

Battery dispatch capabilities

The hardware-specific parts of battery dispatch (the external-control strategy code and the sign conventions for battery power and grid power) are not configured through the environment. They are per-device capabilities, persisted in the dispatch database and shown and set through the admin dispatch API (/admin/api/dispatch/..., not part of the public, documented contract).

  • Each capability row carries only the evidence that governs it. The dispatch adapter reads every evidence field from exactly one capability, so GET .../capabilities reports it on that row only and null on all others — null means "not applicable to this capability", never "unset":
    • battery_power_sign_convention → battery_discharge_positive
    • grid_power_sign_convention → grid_import_positive
    • write_path_convention → soc_strategy_external_code

A PUT that sets an evidence field on a capability that does not govern it is refused with 422 instead of storing a value the adapter would ignore. The same rule covers the remaining evidence fields: enum_byte_width, bool_byte_width, write_frame_layout_verified and apply_sequence_verified belong to write_path_convention, and export_limit_zero_blocks_export to export_limit_convention. note is the exception — every capability may carry one.

  • PUT replaces the capability record; it is not a partial update. An omitted evidence field is reset to its assumption default rather than kept, so a value that was set earlier is lost unless the request sends it again. Read the capability first and resend the fields you want to keep.

  • soc_strategy_external_code is returned as the raw register value, since the RCT register catalog carries no enum label table for it (the meaning is device/firmware-specific, not a project-wide constant). It is only interpretable together with note, so setting write_path_convention to verified is refused with 400 unless the PUT supplies a non-empty note; record there what the code means and what was observed (hardware model, firmware, behavior).

  • Shipping state is unverified. A fresh database ships every capability as unverified with assumption defaults the adapter works with (for example battery_discharge_positive = true, grid_import_positive = true). An unverified required capability blocks the dispatch mode it guards, for that device only.

  • Verification is per device, not per model. Verifying device A never releases device B, even of the identical model and firmware. The only supported transfer is an explicit capabilities:copy-from call naming the source device and the target model/firmware; it copies only capabilities whose evidence matches, and logs each copied row at WARNING. A firmware update invalidates the capabilities it affects; re-verify after updating.
  • Engineering mode is the only way to dispatch on unverified hardware. It is a per-device switch (PUT /admin/api/dispatch/devices/{device_id}), carries a shorter TTL cap than normal operation, and still refuses the write-path capability without a strategy code — there is no way to form the write at all without one.
  • Work through the capability points on the real device using the project's internal hardware verification plan before enabling dispatch in production; it is not part of this documentation site, because a filled-in sheet holds operator measurements that belong with the operator, not on a published page.
  • A removed device loses its dispatch state. Removing a device (or re-addressing it under the same id) resets all its capabilities to unverified, switches engineering mode off and sets the Energy Manager mode to Off, so a device later added under that id starts unverified. The reset runs only after the new device graph was built.
  • A capability or device-limit change is refused while an operation it affects is active. Flipping a sign convention, re-verifying the write path, or changing the power limits/ engineering-mode switch of a device with a running dispatch answers 409 dispatch_capability_conflict and names the blocking operation, instead of taking effect live in the middle of an apply/control cycle. Stop or let the operation finish first.

A device stuck in fault_restore_pending (the restore to the original inverter settings itself failed) is retried automatically by the dispatch cycle, instead of staying stuck until an operator calls cancel/submit again. The delay between attempts doubles from 1 s up to 30 s; there is no attempt limit. The Energy Manager admin status carries the failed attempts (restore_attempts) and the next retry time (next_restore_at).

Protocol catalog

app/catalog/objects.json ships 894 of the 895 IDs from the supplied protocol PDF v1.14 (without wifi_password). The shipped write-policy seed describes 893 scalar objects; the GUI manages actual write approvals in data/rct.db. Existing friendly names stay stable; additional names replace dots and brackets with underscores. net_slave_data remains a structured diagnostic read. Catalog and policy seed are packaged application data; the two former project-root JSON files have been removed. The write reference rctpower_writesupport at 4a0d2e9 informed the ten supported parameters and the one-byte encoding of the 15 enum objects.